Eight-point positive-logic Field Control output module with electronic short-circuit and overcurrent protection for each 24 V DC load point.
What matters when specifying IC670MDL730
|
8 protected outputs
One positive-logic group; every point has electronic short-circuit, overcurrent and MOV protection. |
2 A per point
Check both the 2 A point limit and the 8 A total-module limit when grouping field loads. |
External load supply
The BIU powers module electronics; an 18–30 V DC field source must power the connected loads. |
Point diagnostics
Green status and yellow fault indicators help technicians isolate an output wiring or load problem. |
Description and purpose
|
IC670MDL730 is the Field Control output module for eight 24 V DC positive-logic loads. The host writes one byte of output data through the Bus Interface Unit, while the module reports individual electronic overcurrent or short-circuit faults so maintenance staff can identify the affected point without treating the complete station as one undifferentiated fault. For replacement work, verify the full IC670MDL730 nameplate, installed BIU type and revision, terminal-base keying, shared group reference and total connected current. The outputs are not isolated from one another; the external supply and common arrangement must therefore match the existing field circuit. |
Purchase verificationSend the complete module and BIU labels, terminal-base and connector photos, load type, per-point current, external supply voltage, quantity and destination. Myrtle will compare the supplied identity and installation details before quotation.
|
Technical specifications
Values restated from GE Fanuc Field Control documentation GFK-1288B and GFK-0826J. Confirm the supplied-unit label and installed system before replacement.
Replacing an output module in an installed I/O station?
Share the IC670MDL730 nameplate, BIU catalog number and revision, terminal-base wiring, load current and external supply details. We will check the stated configuration before quotation and flag any point that still needs confirmation.
|
✓ Nameplate and BIU revision
|
✓ Load and field-supply check
|
✓ Terminal-base verification
|
| Email Myrtle · sales5@askplc.com | Open WhatsApp · +86 18950128464 |
Applications
|
Solenoids and valves
Switch 24 V DC actuators after checking continuous and inrush current. |
Motor-starter control
Drive compatible DC coils with appropriate inductive-load protection. |
Panel indicators
Operate status lamps or annunciation loads from Field Control stations. |
Installed-system repair
Restore an existing eight-point protected output group after full wiring verification. |
Ordering information
|
Payment
T/T |
Port
Xiamen |
Delivery time
3–5 days |
Condition
In stock |
Product image and identification notes
![]() |
What buyers should confirm in the photosUse clear front and side views to confirm the complete IC670MDL730 marking, the eight green status indicators, eight yellow fault indicators and green PWR indicator. Photograph the terminal-base keying and all field connections before disconnecting an installed unit. Compare the BIU label and revision, terminal-base arrangement, external supply polarity and connected-load wiring. A similar Field Control housing does not prove electrical interchangeability. Buyer tip: Request current photos of the module face, full nameplate, terminal base and installed BIU before stock confirmation.
|
FAQ about IC670MDL730
|
Is IC670MDL730 a direct replacement for every 8-point Field Control output module?
No. Match the complete IC670MDL730 nameplate, terminal-base wiring, positive-logic load circuit and installed Bus Interface Unit. For a Genius station, GE specifies IC670GBI002 revision 2.10 or later; Profibus and Interbus-S BIUs require version 1.0 or later.
|
Can IC670MDL730 power the connected 24 V DC loads by itself?
No. Backplane power from the BIU operates the module electronics, but the field loads require an external 18–30 V DC source. Confirm polarity, common wiring and the available field-supply current before energizing the station.
|
|
How much load can each IC670MDL730 output switch?
Each point is rated for up to 2.0 A continuous, while the eight-point module is limited to 8 A total. A point may accept up to 10 A inrush for 10 ms, so check both steady current and the starting current of contactors, solenoids or lamps.
|
What does a yellow fault LED on IC670MDL730 mean?
Each output has its own yellow fault indicator. It reports the electronic overcurrent or short-circuit condition for that point. Isolate the load, inspect wiring and current demand, then correct the field fault before returning the output to service.
|
|
Are the eight IC670MDL730 outputs isolated from one another?
No. The eight outputs form one group and do not have point-to-point isolation. Review shared references, grounding and field-supply segmentation; do not assume a visually similar channel can be wired as an isolated output.
|
Which details should I send before requesting an IC670MDL730 quote?
Send the full nameplate, BIU model and revision, terminal-base and connector photos, load type, point current, external supply voltage, quantity and destination. These details let Myrtle check the exact module identity and installation fit before quotation.
|
About PLCEXPORT
PLCEXPORT supports maintenance, engineering and procurement teams sourcing industrial automation components. We review model identity, visible condition and delivery details before quotation.
Recommended models
Published product links are grouped by brand; this selection is arranged for the IC670MDL730 page.
Allen-Bradley
GE
Others - other recommended brands
|
Schleicher XCx 300
|
Saia PCD3.M5560
|
Berghof C-PRO 13
|
KEB C6 COMPACT 2
|
|
Elrest CM211
|
Eaton XC-303
|
LS Electric XGB XEC
|
Panasonic FP7 CPS41E
|
|
AutomationDirect BRX BX-DM1E
|
Turck TBEN-L5-8DIP-8DOP
|
B&R X20CP0484
|
Beijer X2 control 15
|
|
ICP DAS XP-9188-IoT
|
Fatek FBs-32MCT2
|
Horner OCS HE-X10S
|
Lütze LOCC-Box-Net
|
|
Parker PAC320-CWB21-3X
|
Yaskawa MP3300iec
|
Nidec C200-044
|
Mitsubishi Alpha2 AL2-24MR-D
|
|
DIRECT SALES SUPPORT · FIELD CONTROL
Need a verified IC670MDL730 for an installed I/O station?Share the nameplate, BIU revision, terminal-base photos, load details, quantity and destination. Myrtle will review the model identity and shipping requirements before quotation. |
|
| WhatsApp · +86 18950128464 | Email Myrtle · sales5@askplc.com |
Hot Tags: allen-bradley 1746-ib16 slc 500 16-point dc input module, China allen-bradley 1746-ib16 slc 500 16-point dc input module manufacturers, suppliers, 1746 OA16 pdf, 1746-OA16, 1771 P5 Allen Bradley, 1771 P5 manual, 1771-P5, allen bradley plc module