Allen-Bradley 1794-IB32 FLEX I/O Digital Input Module

Allen-Bradley 1794-IB32 FLEX I/O Digital Input Module

ALLEN-BRADLEY · FLEX I/O DIGITAL INPUT
1794-IB32 FLEX I/O Digital Input Module

High-density 24 V DC FLEX I/O module with 32 current-sinking inputs for distributed discrete-signal acquisition.

New & original
One-year warranty
3–5 days
Condition: In stock
Send Inquiry
Description

 

ALLEN-BRADLEY · FLEX I/O DIGITAL INPUT

Allen-Bradley 1794-IB32 FLEX I/O Digital Input Module

High-density 24 V DC FLEX I/O module with 32 current-sinking inputs for distributed discrete-signal acquisition.

New & original
One-year warranty
3–5 days
Condition: In stock
Request a quote

Description and purpose

The Allen-Bradley 1794-IB32 is a 32-point, current-sinking FLEX I/O digital input module for nominal 24 V DC signals. Rockwell Automation specifies a 19.2…31.2 V DC on-state range, selectable input filtering and 50 V continuous basic isolation between field and system. Correct adapter revision, terminal base, sensor polarity and filter setting should be reviewed before replacement.

Technical specifications

Rockwell Automation 1794-IB32 product page · 1794-IN093I-EN-P

Model
1794-IB32
Manufacturer
Allen-Bradley / Rockwell Automation
Product family
FLEX I/O
Input type
32 current-sinking inputs
Nominal input voltage
24 V DC
On-state voltage
19.2…31.2 V DC
On-state current
2.0…6.0 mA · 4.1 mA nominal
Off-state limits
5.0 V DC · 1.5 mA maximum
Nominal input impedance
22.2 kΩ
Input filter
0.25 · 0.5 · 1 · 2 · 4 · 8 · 16 · 32 ms
Field-to-system isolation
50 V continuous, basic insulation
Channel isolation
No isolation between individual inputs
Flexbus current
25 mA at 5 V DC
Terminal base
1794-TB32 or 1794-TB32S
Operating temperature
0…55 °C
Country of origin
Malaysia

Applications

Sensor and limit-switch inputs
Distributed machine status monitoring
Panel space optimization
FLEX I/O input replacement

Ordering information

Payment
T/T
Port
Xiamen
Lead time
3–5 days
Condition
In stock
BUYER QUESTIONS

FAQ about Allen-Bradley 1794-IB32

Will 1794-IB32 work with every 24 V DC sensor?

Not automatically. The module uses current-sinking inputs, so confirm the sensor output type and wiring polarity. Also verify that the signal reaches the specified 19.2…31.2 V DC on-state range.

Why might a fast sensor pulse be missed by 1794-IB32?

The configured input filter can be set from 0.25 to 32 ms. A long filter suppresses noise but can also reject short pulses. Compare the sensor pulse width with the filter setting in the adapter or controller configuration.

Can I replace 1794-IB32 without checking the FLEX I/O adapter revision?

No. Rockwell lists minimum compatible revisions for Remote I/O, ControlNet, DeviceNet, EtherNet/IP and PROFIBUS adapters. Identify the installed adapter and firmware before planning the exchange.

Is each 1794-IB32 input isolated from the others?

No. Rockwell specifies basic isolation between the field side and system, but no isolation between individual channels. Review commons, grounding and field-supply grouping when troubleshooting noise or potential differences.

Which terminal base should I verify for 1794-IB32?

The installation instructions use 1794-TB32 or 1794-TB32S for this 32-point wiring layout. Confirm the installed base and terminal assignments before moving conductors.

What should I send for a 1794-IB32 quotation?

Provide the complete model and series, quantity, adapter type and revision, terminal-base part number, sensor output type, label photos and destination. Include any compatibility problem you are trying to solve.

PLCEXPORT support for FLEX I/O projects

PLCEXPORT helps maintenance and project teams compare nameplate details, review configuration requirements and coordinate international supply for 1794-IB32.

Our team, workplace and order preparation

 
China sales and support team

Myrtle and the sales team coordinate model identification, quotations and international order communication.

 
Technical discussion

Product series, configuration, wiring and compatibility details are reviewed before a supply option is proposed.

 
Warehouse verification

Visible labels, series information and package condition are checked during order preparation.

 
PLCEXPORT China

We support maintenance and project buyers sourcing current and legacy automation components.

FLEX I/O SUPPORT

Need help confirming 1794-IB32 compatibility?

Send Sales Manager Myrtle the complete catalog number, series or revision, quantity, installed-system details and destination. We will review the request before quotation and identify any wiring, firmware or accessory details that still need confirmation.

Recommended Models

Published product references are grouped by brand; each card shows the model only.

ABB - published product references

SIEMENS - published product references

Other recommended brands

Maple Systems HMI5070LB
Kinco MK070E
Delta AH500
Koyo CLICK C0-11DRE-D
Unitronics V700-T20BJ
Horner OCS XL4
Phoenix Contact ILC 131 ETH
Beckhoff CX9020
Wago 750-8212
Turck TBEN-S2-4AI
Moxa ioLogik E1262
Opto 22 SNAP-PAC-R1
Red Lion DA70A
Eaton easyE4-UC-12RC1
LS Electric XBC-DN32U
Panasonic AFP7CPS41E
Fuji NP1PS-74R
CTC Parker PowerStation

 

Hot Tags: allen-bradley 1794-ib32 flex i/o digital input module, China allen-bradley 1794-ib32 flex i/o digital input module manufacturers, suppliers, 1746 OA16 pdf, 1746-OA16, 1771 P5 manual, 1771-P5, Allen Bradley 1746 OA16, Allen Bradley 1746 OA16 Output Module PLC Module