Allen-Bradley 1771-OMD PLC-5 220 V AC Output Module

Allen-Bradley 1771-OMD PLC-5 220 V AC Output Module

ALLEN-BRADLEY · 1771 PLC-5 I/O

Allen-Bradley 1771-OMD PLC-5 220 V AC Output Module

PLC-5 sixteen-point AC output module for 184–250 V AC loads, with a 2 A per-output rating and 8 A module limit.

New & originalOne-year warranty3–5 daysCondition: In stock
Sales Manager: Myrtle · sales5@askplc.com · WhatsApp +86 18950128464
Send Inquiry
Description

↵

Product Information Product Images Company Contact Recommended Models

ALLEN-BRADLEY · PLC-5 AC OUTPUT

Allen-Bradley 1771-OMD PLC-5 220 V AC Output Module

PLC-5 sixteen-point AC output module for 184–250 V AC loads, with a 2 A per-output rating and 8 A module limit.

New & original
One-year warranty
3–5 days
Condition: In stock
Request a Quote

Product at a glance

Key selection points for the 1771-OMD 16-point 184–250 V AC output module.

OUTPUTS
16 AC outputs
Verify each load current and the total module current before connection.
VOLTAGE
184–250 V AC
Use only compatible 47–63 Hz AC field loads.
WIRING ARM
1771-WH family
Match the field wiring arm and preserve terminal identification.

Description and purpose

The 1771-OMD is a sixteen-point PLC-5 AC output module for 184–250 V AC field loads. Each output is rated up to 2 A, but the combined steady-state load must not exceed 8 A for the module.

This module uses a 1771-WH-series field wiring arm and a common 10 A, 250 V fuse. Before replacement, record the wiring-arm terminals, confirm load inrush and leakage compatibility, remove field and backplane power, and inspect the complete nameplate.

Purchase verificationSend the complete 1771-OMD nameplate, installed-system details, terminal or connector photos, required quantity and destination. Myrtle will compare the requested configuration before quotation.

Technical specifications

Values restated from Rockwell Automation publication 1771-TD182. Confirm the complete supplied-unit nameplate and installed configuration.

Model
1771-OMD
Manufacturer
Allen-Bradley / Rockwell Automation
Product family
1771 PLC-5 I/O
Product type
AC output module
Output points
16
Operating voltage
184–250 V AC, 47–63 Hz
Continuous current
2 A per output; 8 A per module maximum
Surge current
25 A per output for 100 ms; 25 A per module for 100 ms
Minimum load
10 mA at 220 V AC
Off-state leakage
4 mA maximum
Fuse
Single 10 A, 250 V fuse
Field wiring arm
1771-WH, 1771-WHF or 1771-WHFB
1771 PLC-5 I/O CONFIGURATION SUPPORT

Planning a 1771-OMD replacement or new installation?

Share the complete nameplate, installed hardware, field wiring or network details, project revision, quantity and destination with Sales Manager Myrtle. We will review the stated configuration and identify any compatibility point that still needs confirmation.

Applications

AC contactor controlSwitches compatible 220 V AC coils after inrush review.
Solenoids and actuatorsDrives supported AC loads within per-point and module limits.
PLC-5 maintenanceReplaces an installed 1771-OMD while retaining the wiring arm.
Legacy panel serviceRestores sixteen AC output points after fuse and load checks.

Ordering information

PaymentT/T
PortXiamen
Delivery time3–5 days
ConditionIn stock
BUYER QUESTIONS

FAQ about 1771-OMD

Can every 1771-OMD output carry 2 A at the same time?
This module uses a 1771-WH-series field wiring arm and a common 10 A, 250 V fuse. Before replacement, record the wiring-arm terminals, confirm load inrush and leakage compatibility, remove field and backplane power, and inspect the complete nameplate.
Will the 1771-OMD off-state leakage keep a small load partially energized?
Use the published selection values together: 16 AC outputs; 184–250 V AC; 1771-WH family. Confirm the project setting and field device rather than relying on appearance.
Which field wiring arm must be present for a 1771-OMD replacement?
Remove system power and document every terminal, common, connector or network setting before moving hardware. Compare the complete 1771-OMD label with the installed assembly.
How should motor-starter or solenoid inrush be checked against 1771-OMD ratings?
Start with the power source, field wiring or network connection, terminal seating and controller configuration. Then compare status indications with the official troubleshooting guidance for 1771-OMD.
What should I inspect if all outputs stop after one field fault?
Do not assume a matching base number proves interchangeability. Verify the full suffix, hardware revision, firmware support and installed-system catalog before replacement.
What load and wiring information should accompany a 1771-OMD request?
Send the full 1771-OMD nameplate, clear front and side photos, connected hardware, project or wiring details, quantity and destination. This lets Myrtle confirm the exact configuration before preparing the offer.

About PLCEXPORT

PLCEXPORT supports maintenance, engineering and procurement teams sourcing industrial automation components for active and legacy systems.

 
Configuration review
Our team compares complete catalog numbers, suffixes and installed-system details before quotation.
 
Global sourcing
PLCEXPORT coordinates verified automation-parts supply for maintenance and project teams.
 
Inspection and packing
Visible labels, interfaces and package condition are reviewed during order preparation.
 
Customer support
Myrtle follows model checks, quotation details and international delivery communication.

Recommended models

Published product links are grouped by brand; this combination is arranged for the 1771-OMD page.

Allen-Bradley

ABB

Others - other recommended brands

Nidec C200-064
PMA KS98-2
Sorel XHCC
Toshiba V200-16MR
Teco SG2-20VR
Wieland samosPRO
Fatek FBs-40MA
ICP DAS WP-8441
B&R X20CP1586
Unitronics USC-B10-T24
Phoenix Contact AXL F 2152
Bosch Rexroth XM21
Wago PFC200
Bachmann MX213
Keba C5-IPC
Aaeon BOXER-6641
Advantech APAX-5580
Lütze 716425
Elmo G-MAS
Festo CPX-E-CEC
Gefran GFX4-IR
Jetter JC-440
Kontron KBox-A-150
Lenze c550
BUYER SUPPORT · 1771 PLC-5 I/O

Confirm the exact 1771-OMD before ordering

Share the full nameplate, installed configuration, clear connector or terminal photos, quantity and destination. Myrtle will review the model identity and compatibility points before quotation.

✓ Nameplate reviewThe complete model and suffix are checked.
✓ Installed systemController, rack, wiring or network details are compared.
✓ Visual verificationCurrent product and connector photos reduce mismatch risk.
✓ Clear quotationQuantity and destination are confirmed before the offer.

Hot Tags: allen-bradley 1771-omd plc-5 220 v ac output module, China allen-bradley 1771-omd plc-5 220 v ac output module manufacturers, suppliers, 1746 OA16 manual, 1746 OA16 pdf, 1771 P5 Allen Bradley, 1771 P5 manual, allen bradley, allen bradley plc module

Send Inquiry