GE IC200ALG264A VersaMax 15-Channel Analog Current Input Module
Fifteen single-ended current inputs with 15-bit conversion in one shared-return group. One carrier jumper selects 4–20 mA or 0–20 mA for the complete module, so range, loop power and common wiring should be checked together.
What matters when specifying IC200ALG264A
15 current inputsSingle-ended channels share one common return and deliver 15 input words to the controller. |
One group-wide rangeNo jumper selects 4–20 mA; a jumper from A16 to A17 selects 0–20 mA for all channels. |
External loop powerBackplane power operates the module, while transmitters and current loops still require an external field supply. |
Diagnostic limitsOpen-wire reporting is available per channel in 4–20 mA mode, but not in 0–20 mA mode. |
Description and purpose
|
IC200ALG264A brings fifteen process-current signals into a VersaMax CPU or network interface through one high-density module. Because every channel is single-ended and shares one return, users should review the common reference, shield grounding and external loop supply before moving existing wires. The carrier jumper applies one range to the whole input group: no jumper for 4–20 mA, or A16–A17 linked for 0–20 mA. This is not a channel-by-channel setting. Confirm that all fifteen loops use the same range; the module is backplane-powered, but field transmitters still need a suitable external supply. |
Purchase verificationFor a replacement or new station, send the full IC200ALG264A nameplate, carrier model, A16–A17 jumper state, controller or NIU firmware, loop-power voltage and common-return drawing. These details help avoid a visually similar but electrically incompatible installation. |
Technical specifications
Values checked against GE Fanuc VersaMax Modules, Power Supplies, and Carriers User's Manual GFK-1504K, pages 10-43 to 10-46.
Checking an IC200ALG264A replacement or new loop group?
Share the full label, carrier model, range-jumper position, common-return arrangement and field-supply voltage with Sales Manager Myrtle. We will review the installed configuration before quotation.
Applications
Collects fifteen 4–20 mA or 0–20 mA field signals through one module.
Consolidates multiple analog loops where a common-return arrangement is acceptable.
Restores a matching VersaMax point set after jumper, carrier and wiring checks.
Uses 4–20 mA open-wire reporting and OK status during troubleshooting.
Ordering information
T/T
Xiamen
3–5 days
In stock
Product image and identification notes

What to confirm in the photos
The front view should show IC200ALG264A, the green OK indicator and module condition. A second view should show the carrier, A16–A17 range-jumper position and shared-return wiring.
For a replacement, compare the carrier type, connector seating and shield/ground arrangement with the installed station before removing any wire.
FAQ about IC200ALG264A
Is IC200ALG264A a direct replacement for any IC200ALG264 module?
Use the complete A-suffix nameplate when buying. Also compare the carrier, jumper setting, shared common return and controller/NIU support before calling it interchangeable.
Can IC200ALG264A power my 4–20 mA transmitters?
No. Backplane power operates the module, but every field transmitter or current loop needs an external source. Verify polarity, voltage and common-return design before wiring.
How do I select 4–20 mA or 0–20 mA on IC200ALG264A?
Leave the carrier jumper absent for 4–20 mA. Install the jumper from A16 to A17 for 0–20 mA. The selection applies to the complete fifteen-channel group.
Will IC200ALG264A detect a broken signal wire?
Open-wire faults are reported per channel only in 4–20 mA mode. Do not expect the same diagnostic in 0–20 mA mode, where zero current is part of the valid range.
What should I check when the green OK LED remains off?
Check backplane power, internally generated field power, carrier seating, configuration and whether the CPU or NIU recognizes the module. The OK LED is more than a simple power indicator.
What installation detail most affects IC200ALG264A readings?
All fifteen inputs are single-ended and share one return, with no channel-to-channel isolation. Confirm the common path, use suitable shielded wiring and avoid grounding arrangements that introduce unwanted current.
About PLCEXPORT
PLCEXPORT supports maintenance, engineering and procurement teams sourcing industrial automation components for active and legacy systems.
Recommended models
Published PLCEXPORT product links have been refreshed and regrouped for this IC200ALG264A page.
Allen-Bradley
GE
Others - other recommended brands
Confirm the exact IC200ALG264A before ordering
Share the full nameplate, range-jumper state, installed carrier, loop-power diagram, controller or NIU firmware, quantity and destination. Myrtle will review the model identity and compatibility points before quotation.
The complete IC200ALG264A identity is checked rather than the base number alone.
The shared range jumper, common return and external loop supply are reviewed together.
CPU or network-interface firmware and project configuration are compared before replacement.
Quantity, destination, packing and shipment requirements are confirmed before the offer.
Hot Tags: ge ic200alg264a versamax 15-channel analog current input module, China ge ic200alg264a versamax 15-channel analog current input module manufacturers, suppliers, GE Fanuc IC695CPE302, GE IC695CEP001, GE IC695CPE302, IC695CEP001 CEP Carrier Module, IC695CPE302, IC695CPE302 CPU module