The input/output module is a bus-based control interface used to control dual-action equipment such as two-stage fire-resistant rolling shutters, water pumps, and smoke exhaust fans. It is primarily used for position control of fire-resistant rolling shutters, controlling their movement from the upper to the middle position, and from the middle to the lower position, while also confirming the shutter's current position (upper, middle, lower). This module can also be used as two independent input/output modules.
The input/output module has two consecutive coded addresses, with a maximum code of 242. It can receive two different action commands from the controller and provides two different control outputs and confirmation signals for two different inputs.
The required input signal for this module is a normally open switch signal. Once the switch signal is activated, it is sent to the controller via the linkage bus. The controller generates an alarm and displays the address number of the activated device. If the module itself malfunctions, the controller will also generate an alarm and display the module number. This module has two pairs of normally open and normally closed contacts and two sets of active outputs. The input and output circuits have a wiring detection function.
The module uses electronic encoding. After one encoded address is entered, another encoded address is automatically generated as: the entered address + 1. This encoding method is simple and fast.