KJ1501X1-BC2 at a Glance
The KJ1501X1-BC2 powers compatible DeltaV controller and LocalBus hardware. It accepts a nominal 12 VDC or 24 VDC supply and provides 12 VDC, 5 VDC and 3.3 VDC outputs. Its 12 VDC output current depends on the selected input mode and cabinet temperature, so an existing installation should be checked against the full BC2 ratings before replacement.
Emerson Specifications and Ordering Details
Confirm the complete order code and product label before purchase or replacement.
Buyer and Engineering Checks
Match the complete supply identity
Confirm KJ1501X1-BC2, assembly number, hardware revision and carrier arrangement against the installed supply.
Identify the input mode
Check whether the site uses nominal 12 VDC or 24 VDC and verify the measured input against the corresponding allowable range.
Calculate each output load
Check the 12 VDC load at the expected cabinet temperature, then check the combined 10 W budget for the 5 VDC and 3.3 VDC outputs separately.
Review wiring and replacement procedure
Confirm input polarity, alarm connections, system power arrangements and the approved isolation procedure before disconnecting the supply.
KJ1501X1-BC2 Product View

Identification checklist
Match the complete model and order code, product label, terminal layout, power requirements and platform compatibility. A similar enclosure does not prove interchangeability.
Typical Applications
KJ1501X1-BC2 FAQ
It is a DeltaV system DC/DC power supply for compatible controller and LocalBus hardware.
Yes. The documented ranges are 11.4-12.6 VDC and 20.4-28.8 VDC respectively. Output limits differ between the two modes.
The stated 10 W limit is the combined budget for the 5 VDC and 3.3 VDC outputs. Check the 12 VDC output against its separate current rating.
Compare the exact supply and its ratings before substitution. The historical manual gives BC1 a narrower 24 VDC input range; BC3 also has different output ratings.
The BC2 instructions require system power to be removed before the unit is removed or inserted. Follow the site's isolation procedure.
The minimum order is one unit, with a one-year seller warranty. Confirm the required revision, condition, stock and lead time when requesting a quotation.
Company and Export Support




We support industrial automation sourcing with model verification, product photography and export coordination. Send the model, quantity, destination and requested delivery date for a focused quotation.
Request a KJ1501X1-BC2 Quotation