Yokogawa AAI135 8-Channel Isolated Current Input Module

Yokogawa AAI135 8-Channel Isolated Current Input Module

YOKOGAWA · CENTUM VP FIO

Yokogawa AAI135 8-Channel Isolated Current Input Module

AAI135 receives eight isolated 4 to 20 mA field signals, with channel-to-channel isolation for demanding process measurement loops. Brand-new original supply with one-year warranty.

Send Inquiry
Description
YOKOGAWA · CENTUM VP FIO

Yokogawa AAI135 8-Channel Isolated Current Input Module

AAI135 receives eight isolated 4 to 20 mA field signals, with channel-to-channel isolation for demanding process measurement loops.

8, channel-isolated
Input channels
4 to 20 mA
Input signal
25 mA
Allowable input current
290–450 Ω powered
Input resistance

Product overview

AAI135 receives eight isolated 4 to 20 mA field signals, with channel-to-channel isolation for demanding process measurement loops.

What AAI135 is used for

The module conditions field signals for process monitoring and control within compatible Yokogawa field I/O nodes.

Application fields

Used in process plants including chemicals, oil and gas, power, water treatment, pulp and paper, metals and other continuous-process applications.

TS

Technical specifications

Verified operating data for Yokogawa AAI135
Module type
Current input module
Input channels
8, channel-isolated
Input signal
4 to 20 mA
Allowable input current
25 mA
Input resistance
290–450 Ω powered
Accuracy
±16 μA
Data update period
10 ms
Transmitter supply
15.0 V min at 20 mA
Isolation withstand
500 V AC field/system and channels
Maximum consumption
360 mA at 5 V / 450 mA at 24 V
Weight
Approx. 0.30 kg
HART
Available
Confirm the complete suffix, terminal option and environmental rating against the installed system. Cable selection can affect isolation-withstand conditions.

Ordering information

Product number
AAI135
Payment terms
TT
Shipping port
Xiamen
Delivery
3~5 days
Stock
20
Minimum order
1 unit

Need a difficult-to-source automation spare?

Send us the full AAI135 suffix, required quantity and terminal details. We will help review the request and coordinate a practical sourcing response.

BUYER & MAINTENANCE FAQ

Questions to resolve before ordering AAI135

Practical checks for range selection, replacement compatibility and commissioning.

01 · RANGE SELECTION
Can AAI135 mix 1–5 V and −10–10 V signals channel by channel?
No. Yokogawa specifies that the input signal selection is set together for CH1 through CH16. Confirm the common range used by the intended module before commissioning.
02 · REPLACEMENT MATCH
Is the AAI135 base model enough to approve a replacement?
No. Verify the full suffix, terminal block or cable interface, environmental option and node compatibility. These details determine whether the spare matches the installed wiring and cabinet conditions.
03 · INPUT PROTECTION
What input limit should be reviewed before connecting an AAI135?
The allowable input voltage is ±30 V. Review field signal scaling, grounding and transient conditions so the module is not exposed beyond the specified limit.
04 · POWER-OFF BEHAVIOR
Why does AAI135 input resistance matter during shutdown work?
Yokogawa lists 1 MΩ with power on and 200 kΩ with power off. Maintenance teams should consider this change when assessing the connected circuit during outage testing.
05 · REDUNDANCY
Can AAI135 be installed in a dual-redundant configuration?
Yes. The module supports dual redundancy. Confirm identical compatible modules, node support and the engineering configuration before replacement.
06 · RECEIVING CHECK
What should be checked when an AAI135 arrives?
Inspect the front label, complete suffix, connector pins and housing. Compare the supplied interface accessories with the purchase request before functional testing or installation.
SALES CONTACT

Discuss your AAI135 requirement

For a faster review, include the full module suffix, terminal type, quantity and destination.

Automation spare-parts support

PLCEXPORT supports maintenance teams sourcing PLC and DCS components for installed automation systems. Each request is reviewed by model, suffix, quantity and application context so the quotation can reflect the equipment actually required. Product identity should always be confirmed from the nameplate and project documentation.

Model review
Suffix and interface details checked
Supply coordination
Availability aligned to the request
Global dispatch
Destination and delivery needs reviewed
Company photo gallery
 
 
 

Recommended automation models

Each recommendation set is unique to this product page. Verify platform, function and wiring independently.

Honeywell

GE

Others · Other recommended brands

Bachmann CM411SIGMATEK DI412Saia CP413VIPA IO414KEBA CM415Berghof DI416Horner CP417Unitronics IO418Fatek CM419Haiwell DI420Kinco CP421ICP DAS IO422ODOT CM423TRsystems DI424Selec CP425Korenix IO426Turck CM427Jetter DI428Schleicher CP429Crouzet IO430Kollmorgen CM431Pro-face DI432Yaskawa VIPA CP433Gantner IO434
Yokogawa AAI135 · Request a model review

Hot Tags: yokogawa aai135 8-channel isolated current input module, China yokogawa aai135 8-channel isolated current input module manufacturers, suppliers, AAI141 S00 Analog IO Module, AAI841 H00 S2 ATK4A 00 8 channel IO, AAI841 H00 Yokogawa, AAI841 H03 I O, AAI841 H03 S1 Analog I O Module, yokogawa i o module

Send Inquiry