Schneider Electric 140AVI03000 Quantum 8-Channel Analog Input Module

Schneider Electric 140AVI03000 Quantum 8-Channel Analog Input Module

SCHNEIDER ELECTRIC · MODICON QUANTUM
Schneider Electric 140AVI03000 Quantum 8-Channel Analog Input Module
Eight-channel differential multirange analog input module for Modicon Quantum voltage and current signals.
New & originalOne-year warranty3–5 daysCondition: In stock Request a quote
Send Inquiry
Description
SCHNEIDER ELECTRIC · MODICON QUANTUM

Schneider Electric 140AVI03000 Quantum 8-Channel Analog Input Module

Eight-channel differential multirange analog input module for Modicon Quantum voltage and current signals.

Description and purpose

The 140AVI03000 is a Modicon Quantum analog input module with eight differential channels. Each configured channel can measure the documented voltage or current range, including unipolar 0–5 V, 0–10 V and 0–20 mA or bipolar ±5 V, ±10 V and ±20 mA operation.

The module occupies nine input words and applies 16-bit conversion. Channel range, field wiring, shielding and the installed terminal block must match the Control Expert hardware configuration before a replacement is energized.

Purchase verification
Send the complete 140AVI03000 label, terminal block number, channel-by-channel range list, loop-power arrangement, wiring photos and current Control Expert configuration. We will check signal type and lifecycle implications before quotation.

Technical specifications

Schneider Electric 140AVI03000 product data and Quantum Discrete and Analog I/O Reference Manual.

Model
140AVI03000
Manufacturer
Schneider Electric
Product family
Modicon Quantum
Product type
Multirange analog input module
Analog inputs
8 differential channels
Input modes
Unipolar or bipolar voltage/current
Voltage ranges
0–5 V, 0–10 V, ±5 V, ±10 V
Current ranges
0–20 mA and bipolar ±20 mA
Resolution
16 bits
Addressing
9 input words
Filter
Single-pole low-pass; -3 dB at 847 Hz ±20%
Lifecycle
Discontinued; service support per Schneider schedule
CONFIGURATION SUPPORT

Need a precise 140AVI03000 compatibility check?

Send Sales Manager Myrtle the complete nameplate, installed hardware details, required quantity and destination. We will review the configuration points that matter before quotation.

Applications

Process transmitters
Reads configured current loops from compatible pressure, flow, level or temperature transmitters.
Bipolar measurement
Acquires positive and negative voltage/current signals from compatible test or drive equipment.
Quantum rack maintenance
Restores eight analog channels in an existing Modicon Quantum I/O drop.
Plant modernization planning
Keeps a legacy Quantum signal set documented while an engineered migration is evaluated.

Ordering information

Payment
T/T
Port
Xiamen
Lead time
3–5 days
Condition
In stock
BUYER QUESTIONS

FAQ about 140AVI03000

Can I wire 4–20 mA transmitters directly to 140AVI03000?

The module supports current measurement within its documented 0–20 mA range, but the loop-power source, polarity, terminal assignment and channel configuration must be confirmed. Keep the existing loop diagram and verify each channel in Control Expert.

Can voltage and current inputs be mixed on one 140AVI03000?

Use only combinations allowed by the module configuration and terminal wiring. Record the selected range for every channel and compare the existing field circuit before moving conductors; a visually similar terminal position does not confirm the correct signal mode.

Is 140AVI03000 an isolated analog input module?

Do not infer channel isolation from the product name. Schneider identifies this as an eight-channel differential multirange module; verify the grounding, common-mode and isolation requirements in the Quantum reference manual for the installed application.

What should be backed up before replacing 140AVI03000?

Save the Control Expert project and capture each channel range, scaling, alarm handling and rack address. Photograph the terminal block before removing it and label every conductor so polarity and shield routing are preserved.

What does Schneider recommend as a migration replacement for 140AVI03000?

Schneider lists BMXAMI0810 as a recommended X80-family replacement, but it is not a drop-in Quantum module. A migration requires a new rack/interface, wiring and application engineering review.

What information is required for a 140AVI03000 quotation?

Provide the full nameplate, terminal block, rack and slot, eight channel ranges, field voltages/currents, shielding method, quantity and destination. This lets the supplied module and support path be evaluated against the real installation.

About PLCEXPORT

PLCEXPORT supports maintenance, engineering and procurement teams sourcing industrial automation components for active and legacy systems.

 
Configuration review
Our team compares complete catalog numbers, suffixes and installed-system details before quotation.
 
Global sourcing
PLCEXPORT coordinates verified automation-parts supply for maintenance and project teams.
 
Inspection and packing
Visible labels, interfaces and package condition are reviewed during order preparation.
 
Customer support
Myrtle follows model checks, quotation details and international delivery communication.

Recommended models

Published website references are grouped by brand; each card shows the model only.

GE

Bently Nevada

Others - other recommended brands

DIRECT SALES SUPPORT

Trying to secure a verified 140AVI03000?

Share the complete identification, configuration, quantity and delivery destination with Myrtle. We will organize a focused model check before preparing the offer.

Hot Tags: schneider electric 140avi03000 quantum 8-channel analog input module, China schneider electric 140avi03000 quantum 8-channel analog input module manufacturers, suppliers, 140ACO02000 SCHNEIDER, 140CPU67160, 140CPU67160 SCHNEIDER, Modicon Quantum 140NOE77101, modicon quantum series, Schneider 140NOE77101

Send Inquiry