Products Description
The MC-TAOX12 Analog Output Module (Part Number: 51304335-125) is a precision industrial output module designed for Honeywell control systems. Its primary function is to convert digital signals from a controller into proportional analog signals (typically 4–20 mA or 0–10 V) for controlling valves, actuators, and other process equipment. Unlike general-purpose output modules, the MC-TAOX12 is engineered for high accuracy, fast response, and reliability in demanding industrial environments, ensuring that critical control loops receive stable, repeatable analog signals every time. Its robust design supports both continuous and dynamic control applications.
Contact Us to Get the Best Price
| Sales Person | Felicia |
| Whatsapp/Wechat | +86 18030132586 |
| cn@mooreplc.com | |
| Phone Number | +86 18030132586 |
Product Specifications
| Item | Specification |
|---|---|
| Part Number | 51304335-125 |
| Channels | 16, individually isolated |
| Signal Type | 4–20 mA current sourcing |
| Load Resistance | 0–750 Ω (including wire) |
| Accuracy | ±0.1 % of span (25 °C) |
| Temperature Drift | ≤ 0.6 µA/°C |
| Update Time | < 2 ms (all channels) |
| HART Pass-through | Yes, Burst mode 0–3 |
| Isolation | 3 kV channel-to-bus, 250 V channel-to-channel |
| Power (5 Vdc rack) | 1.2 A typical, 1.6 A max |
| Power (24 Vdc field) | 390 mA shared, current-limited |
| Conformal Coating | Acrylic, IEC 61086, RTIII |
| Operating Temp | 0 °C to +60 °C (IEC 60654-1 Class B) |
| Storage Temp | –40 °C to +85 °C |
| MTBF | 318,000 h @ 40 °C (MIL-HDBK-217F) |
| RoHS/REACH | Fully compliant |
Importance of this Item
While the designation MC-TAOX12 identifies the general hardware family, the full part number 51304335-125 specifies a unique revision with key enhancements that ensure reliable, compliant operation. This version features a RoHS-compliant conformal coating for long-term environmental protection, and 3 kV galvanic isolation between channels and the bus, safeguarding against electrical faults and cross-channel interference. Additionally, it incorporates an upgraded 40 MHz ASIC, which reduces update latency to under 2 milliseconds, improving response time for fast control loops. These improvements make the 51304335-125 module the only direct replacement that maintains SIL-rated loop integrity without the need for additional proof-test documentation. By specifying this exact revision, operators and engineers can confidently upgrade or maintain systems, ensuring full compatibility, compliance, and performance in critical industrial applications. This precision is especially important in automated and safety-instrumented systems where reliability cannot be compromised.
Industrial Applications
The Honeywell MC-TAOX12 51304335-125 Analog Output Module is widely used across diverse industrial sectors where precise and reliable analog control is critical. In process control plants, including chemical, petrochemical, and refining facilities, it manages flow, pressure, and temperature loops to ensure safe and efficient operations. In power generation, it controls boiler and turbine actuators, enabling accurate load regulation and stable energy output. Water and wastewater treatment facilities rely on this module for precise control of pumps, valves, and level-sensing systems, maintaining consistent water quality and flow rates. In HVAC applications, the module modulates valves, fans, and dampers to optimize climate control and energy efficiency. Manufacturing automation benefits from its high-speed and stable analog outputs to control motors, actuators, and other critical equipment, enhancing production accuracy and process consistency. Its versatility, fast response, and robust design make it ideal for any industrial environment demanding precise analog control.
FAQ
01.Does 51304335-125 support HART multidrop?
Yes-each channel can source up to 4 mA total, allowing up to 3 HART slaves in multidrop mode.
02.Can I use this card on a non-redundant C200 controller?
Absolutely-redundancy is optional; single-module operation is default.
03.What happens if I accidentally short a loop?
04.Will the module accept external 24 Vdc loop supply?
No-loop power is internally derived. Applying external 24 Vdc will void warranty and damage circuitry.
05.Can I mix this revision with older 51304335-100 in the same rack?
Yes-both revisions coexist; however, only 51304335-125 delivers SIL 2 data sheets for new safety loops.
Recommendations
| HCiRX05-TE-FD-NC | 2MLF-HD2A-CC |
| HCiRW05-TE-FD-NC | 2MLF-SOEA-CC |
| HCiRW07-TE-FD-NC | 2MLL-EFMTB-CC |
| HCiRX08-TE-FD-NC | 2MLL-EFMHB-CC |
| HCiRX10-TE-FD-NC | 2MLL-EFMFB-CC |
| HCiRW10-TE-FD-NC | 2MLL-C42B-CC |
| HCiRX12-TE-FD-NC | 2MLL-CH2B-CC |
| HCiRX12-AE-FD-NC | 2MLL-PMEB-CC |
| HCiRX15-TE-FD-NC | 2MLL-PSEA-CC |
| HCiRD10-20S | 2MLL-PSRA-CC |
| HCiRD12-20S | 2MLL-DMEB-CC |
| HCiRD15-20X | 2MLL-DBDT |
| HCiRP-20D | 2MLL-DBDF |
| HCiRD10-10S | 2MLL-DBDH |
| HCiRD12-10S | 2MLL-DBDT-CC |
| HCiRD15-10X | 2MLL-DBDF-CC |
| HCiRP-10D | 2MLL-DBDH-CC |
Hot Tags: honeywell mc-taox12 51304335-125 analog output module, China honeywell mc-taox12 51304335-125 analog output module manufacturers, suppliers