Honeywell FC-SAI-1620M V1.5 Safety Manager System Module

Honeywell FC-SAI-1620M V1.5 Safety Manager System Module

Dimensions: 2x19x12.8cm
Weight: 0.14kg
Contact Sales Felicia for quotation and more info:
Mobile: +86 18030132586
Email: cn@mooreplc.com
Whatsapp(Wechat): +86 18030132586
Send Inquiry
Description

Product Description

 

   The SAI-1620m analog input module provides sixteen safety-rated inputs (0–4 V) plus one external-voltage read-back channel (0–4 V).
All sixteen inputs meet SIL 3 / IEC 61508 requirements and share a single, galvanically-isolated 0 V reference.

Field signals must be scaled to 0–4 V before reaching the module.
   Two conversion options are available:

       1. Use a field termination assembly-TSAI-1620m, TSHART-1620m, TSGAS-1624 or TSFIRE-1624.

       2. Plug an analog conversion card, BSAI-1620mE, into the programming connector (P.) on the rear of the I/O backplane inside the 19-inch chassis.

   Direct connection of thermocouples, PT-100 or other non-current sensors is not supported; they must first be converted to 0(4)–20 mA by a suitable transmitter, then routed through either a TSAI-1620m or BSAI-1620mE module.

product-837-393

 

Our Contact Info

Sales Person Felicia
Mobile +86 18030132586
Email cn@mooreplc.com
Wechat +86 18030132586
Whatsapp +86 18030132586

 

Product Parameters

 

Category Item Specification
General Type numbers FS-SAI-1620m V1.1FC-SAI-1620m CC V1.1FA-SAI-1620m CA V1.1
  Approvals CE, TÜV, UL, CSA, FM
  Space requirements 4 TE, 3 HE (4 HP, 3U)
Power 5 Vdc consumption 35 mA
  24 Vdc consumption 35 mA
Input Number of channels 16
  Input range 0 – 4.1 V
  Input resistance > 1 MΩ
  A/D converter resolution 12-bit
  A/D converter inaccuracy ± 1 LSB
  Module inaccuracy < 0.25 %
  Absolute maximum signal ± 36 Vdc
  Channel crosstalk > 60 dB
External Voltage Read-back Read-back range 0 – 4.1 V
  Read-back input resistance ≈ 1 MΩ
Key Coding Module code holes A5, C25
  Chassis code large pins A5, C25

 

Advantages

 

   The SAI-1620m analog input module is engineered for high-integrity safety systems requiring reliable low-voltage signal acquisition. It offers sixteen SIL 3–rated analog inputs in the 0–4 V range, plus an external voltage read-back channel for enhanced diagnostics. A 12-bit A/D converter with low module inaccuracy (<0.25%) ensures precise and repeatable measurements. All channels share a galvanically isolated 0 V reference, improving noise immunity and system stability. Flexible signal conversion options using field termination assemblies or plug-in conversion cards simplify system design while maintaining strict functional safety compliance.

 

Applications

 

   The SAI-1620m is widely used in safety-critical monitoring applications where accurate analog signal input is essential. Typical uses include reading process values from pressure, flow, level, and gas transmitters that provide 0–4 V or converted 4–20 mA signals. It is commonly deployed in Safety Manager and Safety Manager A.R.T. systems across industries such as oil and gas, chemical processing, power generation, and fire and gas detection. By supporting external signal conversion modules, the SAI-1620m integrates seamlessly with standard industrial transmitters while ensuring SIL 3 compliance and dependable plant protection.

 

Related Honeywell items

 

Model Nominal Input Voltage Output Rating Note / Form Factor
PSU-UNI2450U 24 Vdc 5 A (50 W) Universal 24 V DIN-rail
PSU-UNI4825U 48 Vdc 2.5 A (50 W) Universal 48 V DIN-rail
PSU-UN16020U 60 Vdc 2 A (50 W) Universal 60 V DIN-rail
PSU-UNI11011U 110 Vdc 1.1 A (50 W) Universal 110 V DIN-rail
1200 S 24 P067 24 Vdc 5 A (120 W) 1200-series slim
1200 S 48 P073 48 Vdc 2.5 A (120 W) 1200-series slim
RUSPSU-R 24 Vdc 10 A (240 W) Redundant, hot-swap
RUSPSU-S 24 Vdc 10 A (240 W) Stand-alone version
PSU-UNI2412 24 Vdc 12 A (288 W) Universal high-current
PSUTA-0001 24 Vdc 5 A (120 W) TA-style chassis plug-in

 

FAQ

01.What type of signals does the Honeywell FC-SAI-1620M V1.5 accept?

The FC-SAI-1620M V1.5 accepts up to sixteen safety-rated analog input signals in the 0–4 V range, plus one external voltage read-back channel for diagnostic purposes.

02.Can 4–20 mA field signals be connected directly to the module?

No. Field signals must be converted to 0–4 V before reaching the FC-SAI-1620M, using approved field termination assemblies or conversion modules.

03.Which conversion options are supported for signal scaling?

Signal conversion can be achieved using field termination assemblies such as TSAI-1620m, TSHART-1620m, TSGAS-1624, TSFIRE-1624, or by installing a BSAI-1620mE conversion card in the rear connector.

04.Does the module support direct connection of temperature sensors?

Direct connection of thermocouples, PT-100, or other non-voltage sensors is not supported. These sensors must first be connected to a suitable transmitter.

 

Recommendations

 

51451432-010 330103-00-06-10-12-00 51402497-200 330703-000-050-10-12-00
51451432-020 330103-00-19-10-12-00 TP-DSOEP1-100 330104-05-10-50-02-00
51205995-501 330103-00-08-10-12-00 TP-OPADP1-200 330904-00-25-50-02-00
50008930-001 330103-00-11-10-12-00 8C-PCNT01 330101-00-12-15-02-00
50008930-002 330103-00-05-10-12-00 8C-TCNT01 330702-00-10-10-01-00
50047098-001 330103-00-18-10-12-00 8C-PCNT02 514543363-275 330102-05-30-50-02-05
900CR15-00 330104-00-10-05-02-05 CC-HCAR01 51454504-175 21000-00-00-00-00-02
900CR10-00 330104-00-16-05-02-05 8C-PCNT03 330101-00-22-10-02-05
900CR07-00 330104-00-08-05-01-05 51402497-200 TP-DSOEP1-100 330103-00-11-50-02-05
900CR04-00 330104-00-08-50-01-05 CC-TFB412 330851-02-000-030-10-00-05
900CRAD-10 330101-00-25-20-12-05 CC-PFB401 330905-00-05-10-02-05
900G3AD-15 330101-00-55-20-12-05 10018/E/E 330130-085-02-00
900CP1-0300 330101-00-28-20-12-05 10006/2/1 330980-51-05
900SP1-0300 330104-04-10-10-02-05 520MD+37-W2D200-GM3 330104-03-12-10-02-00
900RNF-0200 330704-000-050-90-02-05 3200MD-28-D6-E-04-40-0G-00 330104-00-13-15-01-00

 

Hot Tags: honeywell fc-sai-1620m v1.5 safety manager system module, China honeywell fc-sai-1620m v1.5 safety manager system module manufacturers, suppliers