Products Description
The 10310/2/1 module is an earth leakage detector (ELD) for 24 Vdc systems. It has a manually operated self-test and earth connection monitor (switch 2 in 'TEST' position).
The ELD can be used to monitor: 24 Vdc, 48 Vdc and/or 60 Vdc systems, or 110 Vdc systems.
The ELD module connects earth level with -12 Vdc (referenced to the 0 V connection of the 24, 48, 60 and/or 110 Vdc supply). This connection is:
· continuous (switch 1 in 'DC' position), or
· interrupting at 1 Hz (switch 1 in '1 Hz' position), or
· interrupting at 0.25 Hz (switch 1 in '1/4 Hz' position).

With switch 1 in the '1 Hz' or '1/4 Hz' position, the green MODE LED on the module front flashes at the selected connection frequency.
Switch 1 is normally used in the 'DC' position.
The '1 Hz' position should only be used to accommodate for solenoids or relays that could stay energized by the negative earth voltage.
The '1/4 Hz' position can be used for locating earth faults. Locating earth faults requires a current clamp (e.g. the C37 clamp from Chauvin Arnoux) and a voltmeter (200 mV AC range).
An earth fault sets the flip-flop (FF), and de-energizes the relay. The flip-flop remains set until a reset is given. This can be done in three ways:
• manually (by setting switch 2 to 'RESET' position), or
• by a high level at the Rst24 input, or
• by a high level at the Rst110 input.
The ELD module can be tested by connecting a 1.5 kOhm resistor between 0 V and earth. This should set the flip-flop. A 1.5 kOhm resistor in the ELD with its own connection to earth (on the Earth2 pin) allows testing of the ELD and the earth connection (switch 2 in 'TEST' position). A disconnected Earth1-to-Earth2 link will block the flip-flop set action (because no earth current is flowing).
Contact Us to Get the Best Price
| Sales Person | Felicia |
| Whatsapp/Wechat | +86 18030132586 |
| cn@mooreplc.com | |
| Phone Number | +86 18030132586 |
Products Parameters
| Category | Parameter | Specification |
|---|---|---|
| General | Type number | 10310/2/1 |
| Power | Supply voltage | 24 Vdc (max. 30 Vdc) |
| Supply current | Max. 60 mA | |
| Reset inputs | Rst24 input voltage | 18 … 70 Vdc |
| Rst24 input current | 1.1 mA at 24 Vdc | |
| Rst110 input voltage | 40 … 130 Vdc | |
| Rst110 input current | 2.5 mA at 110 Vdc | |
| Earth | Earth voltage (no fault) | –12 Vdc |
| Earth voltage (fault) | –30 … +125 Vdc | |
| Earth-fault threshold | 5.5 mA ± 1 mA | |
| Max. earth current | 25.0 mA ± 5 mA | |
| Output contact | Max. output voltage | 115 Vdc |
| Max. output current | 2 A | |
| Relay contacts | Initial contact resistance | 30 mΩ |
| Max. current | 5 A | |
| Max. switched voltage | 250 Vdc / 250 Vac | |
| Max. switched load | 100 W / 1000 VA | |
| Life expectancy | Electrical | 100,000 switch operations |
| Mechanical | 200,000,000 switch operations | |
| Key coding | Module code (holes) | A5, A11 |
| Rack code (large pins) | A5, A11 |
Applications
The Honeywell 10310/2/1 ELD is commonly used in safety-related control systems where uninterrupted DC power integrity is critical. In oil and gas, chemical processing, and power generation plants, the module monitors earth leakage in 24 Vdc to 110 Vdc supply networks feeding control, protection, and shutdown systems. Early detection of earth faults helps prevent insulation degradation, unintended trips, or equipment damage. The selectable monitoring modes allow the detector to adapt to different grounding philosophies used in safety-critical installations.
Advantages
The Honeywell 10310/2/1 Earth Leakage Detector is designed to provide precise monitoring of DC power systems by continuously supervising earth leakage conditions. It supports 24 Vdc, 48 Vdc, 60 Vdc, and 110 Vdc systems, making it suitable for a wide range of industrial applications. The module connects the earth level to –12 Vdc and allows this reference to be applied continuously or intermittently at selectable frequencies of 1 Hz or 0.25 Hz. This flexibility improves fault detection accuracy while reducing the risk of masking intermittent earth faults.
FAQ
01.What is the primary function of the Honeywell 10310/2/1 module?
02.Which DC system voltages can be monitored by the 10310/2/1 ELD?
03.What earth connection modes are available on the 10310/2/1?
04.Does the 10310/2/1 include a self-test function?
05.What is the earth-fault detection threshold of the ELD?
Recommendations
| CC-PCNT01 | TC-FXX071 | P0916WF | 6SN1123-1AA00-0CA2 |
| CC-PAOH01 | TC-CCR012 | FBM215 | 6FC5447-0AA01-0AA0 |
| CC-PAIH01 | 51402573-250 | FBM223 P0917HD | 6SN1146-1AB00-0BA1 |
| CC-PCF901 | 51402573-150 | P0916AA | 6SE7021-0TP50-Z |
| CC-PAIM01 | TC-MUX021 | B0123HE | 6SE7031-2EP85-0AA0 |
| 8C-PAON01 | R8001L8001 | FBM1/37/43 P0400HH | 6SE7021-0EP50-Z |
| 8C-PAIH61 | TK-FPDXX2 | AD916AE | 6SE7023-8TP60-Z |
| 8C-PAIH61 | TK-FTEB01 | FBM202 P0914ST | 6SE7021-3TP50-Z |
| 8C-PAON01 | TC-FXX132 | FBM230 P0926GU | 6SN1111-0AA01-2CA0 |
| CC-PDOB01 | TK-FPDXX2 | AD908AC | 6SE7022-6TP50-Z |
| 6AV7830-0BA10-1CC0 | CC-PDOB01 | P0916VL | 6SE7025-0TP87-2DD0 |
| 6AV7870-0HA20-0AA0 | CC-PDIL01 | P0903CV | 6SE7016-0TP50-Z |
| 6AV7613-0AF32-0CJ0 | CC-PAIX01 | AD916AG | 6SE7021-0TP50-Z |
| 6AV7892-0AD30-1AC0 | CC-PAOX01 | P0972VA | 6SE7021-3TP50-Z |
| 6AV7885-2AA11-1AA4 | MU-FOEA02 | P0916CC | 6ES7023-4TP50-Z |
| 6AV7872-0HA20-0AA0 | TK-PRR021 | P0916VC | 6ES7016-0TP50-Z |
| 6AV7872-1CE54-0AF0 | TC-FXX102 | AD908AA | 6ES7021-0TP50 |
| 6AV7892-0AD30-1AC0 | TC-PRR021 | CP40B | 6SN1123-1AA00-0BA1 |
| 6AV7872-0BD20-0AA0 | TK-PPD011 | IPM2-P0904HA | 6SN1123-1AA00-0HA0 |
Hot Tags: honeywell 10310/2/1 earth leakage detector (eld), China honeywell 10310/2/1 earth leakage detector (eld) manufacturers, suppliers, 10105 2 1 manual, 10215 2 1 meaning, 10006 2 1 manual, honeywell, 10006 21 battery module, Honeywell 10215 2 1